Inspection
Inspection Details
Equipment ID
13753
13753
Inspection Date
6/16/2020
6/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
Slide
TBD
TBD
Governor Rope Pull
TBD
TBD
Door Closing Force
23
23
External ID
1472a8cf-19e4-4dde-9a62-eca90eea33cf
1472a8cf-19e4-4dde-9a62-eca90eea33cf
Location
Ventana Lofts
1635 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 371-0035
1635 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 371-0035
Owner
Attn: Mike McRogerts
Mike McRogerts
104 N Armour, North Kansas City, MO 64116
Phone: (000) 000-0000
Mike McRogerts
104 N Armour, North Kansas City, MO 64116
Phone: (000) 000-0000
Billing
Attn: Ventana Lofts
Bogen Lofts Accounts Payable
1207 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 241-6644
Email: manager@thebogen.com
Bogen Lofts Accounts Payable
1207 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 241-6644
Email: manager@thebogen.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone not working | 1/24/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 4/8/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Car door restrictor shall work. | 4/8/2019 |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | Yes | No | 8.4.10.12(c) - Make repairs or adjustments to the counterweight derailment assembly in the pit. The counterweight hits the counterweight derailment assembly when counterweight buffer is compressed. | 4/8/2019 |
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | No | No | Replace the jewel in the car station to its normal position. | 7/22/2019 |
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | Yes | No | Repair hoist machine leaks. | 6/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. The car top shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room floor shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A monthly fire service testing log shall be completed and kept on-site. | 7/27/2020 |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | Yes | Yes | The governor rope is damaged and shall be replaced. Determine and correct cause of damage. - Elevator Red Tagged | 6/23/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All category 5 testing items still need to be performed and witnessed. | 6/23/2020 |
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | Yes | No | Repair hoist machine leaks. | 6/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. The car top shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The machine room floor shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean. | 7/27/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A monthly fire service testing log shall be completed and kept on-site. | 7/27/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Governor rope has been replaced. While unloading weights to test the new governor rope, an unsafe and dangerous situation was created by a tenet in the building. The elevator was locked out of service and testing will be re-scheduled for a later date. Full testing of governor rope still required. | 6/30/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | The pit shall be kept clean. Clean the pit. | 2/2/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/11/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 3/11/2025 |
| A17.1-1996 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10.1.2 - Protection not functioning | Yes | No | Upon actuation of a seismic detection device, all elevators in modes of operation other than earthquake mode and operations referenced by 8.10.1.3(b) that are in motion shall proceed to the nearest floor. Elevators at a floor upon actuation of a seismic detection device shall remain at the floor, doors shall open and call shall shut down. |