Inspection
Inspection Details
Equipment ID
167
167
Inspection Date
7/25/2020
7/25/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
UNK
UNK
Governor Rope Pull
250/500
250/500
Door Closing Force
23
23
External ID
1f44196e-2f39-49d6-842f-7255f418ea1d
1f44196e-2f39-49d6-842f-7255f418ea1d
Location
Emerson Corporate Office
8000 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
8000 W Florissant Ave, St. Louis, MO
Phone: (314) 553-2229
Owner
Attn: Dan Kohr
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 568-4569
Email: dan.kohr@emerson.com
Emerson Corporate Office
8000 W Florissant, St. Louis, MO 63136
Phone: (314) 568-4569
Email: dan.kohr@emerson.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone does not call Security. It calls a recording. Please reprogram. 1.6 | 1/14/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties set with full capacity and broke. Red tagged. | 8/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean oil & dirt from elevator car top | 12/3/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean oil & dirt from elevator car top. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. | 3/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. | 3/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | There is not “In Case of Fire” signage at each landing as required by the building code. | 12/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 incomplete, lower and hold 125%, unintended motion full load down, car and counterweight buffers need smashed, safeties shall be set with 100% capacity, and slide shall be recorded in order to complete category 5 testing. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Car top lighting inoperable and shall be repaired, or replaced. | 12/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car top light inoperable. Provide means for the car top light to properly function. | 7/20/2026 |