Inspection
Inspection Details
Equipment ID
7652
7652
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Sheraton West Port Chalet
191 West Port Plaza Dr, St. Louis, MO
Phone: (314) 878-1500
191 West Port Plaza Dr, St. Louis, MO
Phone: (314) 878-1500
Owner
Westport Investment Group LLC
940 West Port Plaza Dr, Suite 205, St. Louis, MO 63146
940 West Port Plaza Dr, Suite 205, St. Louis, MO 63146
Billing
Attn: The Sheraton West Port Hotel
900 West Port Plaza Dr, , MO 63146
900 West Port Plaza Dr, , MO 63146
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room door should be locked at all times. | 6/28/2018 |
| conversion | conversion | n/a | No | No | Machine room shall not be used as a storage locker. Clean out items not associated with elevator operation. | 6/28/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Sump pump needs cover. | 3/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher needs to be serviced. | 3/29/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean & dry | 4/10/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light fixture failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. | 5/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7 | 5/1/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry | 5/1/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit to remove debris, water and/or oil and address sources | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide maintenance pit can and drip line. There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The state of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired or replaced. Remove the recovery unit after the packing gland has been repaired or replaced and record the oil loss per A17.1 2016 8.6.5.5.2 |