Inspection
Inspection Details
Equipment ID
13845
13845
Inspection Date
7/15/2020
7/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Ken Koppel
Ken Koppel
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
ec46121e-cfb8-4957-a579-e00c555c3ae9
ec46121e-cfb8-4957-a579-e00c555c3ae9
Location
St. Mary's Medical Bldg
6555 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (636) 926-8900
6555 CHIPPEWA ST, SAINT LOUIS, MO
Phone: (636) 926-8900
Owner
IREMCO, Inc
15510 OLIVE BLVD STE 200, CHESTERFIELD, MO 63017-0710
15510 OLIVE BLVD STE 200, CHESTERFIELD, MO 63017-0710
Billing
Attn: IREMCO, Inc
15510 OLIVE BLVD STE 200, CHESTERFIELD, MO 63017-0710
15510 OLIVE BLVD STE 200, CHESTERFIELD, MO 63017-0710
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | Repair 2nd floor door closer. | 10/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable emergency light. | 7/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram emergency phone to call a monitored emergency number. | 7/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide tested fire extinguisher in machine room. | 10/14/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current elevator certificate. | 10/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not ring to 24/7 support. | 7/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide each piston with own means to collect oil (no sharing). | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP. None | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide updated fire extinguisher in the elevator machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide guard on bulbs in the machine room, to prevent accidental contact or breakage. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room. |