Inspection
Inspection Details
Equipment ID
6199
6199
Inspection Date
7/28/2020
7/28/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Donald Miles
Donald Miles
Relief Valve Pressure
250
250
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
a0d353c3-0f5d-485b-bdff-b083443665b3
a0d353c3-0f5d-485b-bdff-b083443665b3
Location
Stadium Press Box
100 E NORMAL ST, KIRKSVILLE, MO
Phone: (000) 000-0000
100 E NORMAL ST, KIRKSVILLE, MO
Phone: (000) 000-0000
Owner
Attn: Angie Buck
Truman State University
100 E Normal St, Kirksville, MO 63501
Phone: (660) 785-4204
Email: abuck@truman.edu
Truman State University
100 E Normal St, Kirksville, MO 63501
Phone: (660) 785-4204
Email: abuck@truman.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from elevator pit. | 11/28/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide self locking mechanism for machine room door. | 11/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide feed source for main line disconnect. | 11/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide feed source for 110V car light disconnect. | 11/28/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Fire recall module in machine room missing cover. | 11/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide pit container for oil collection in pit not to exceed 5 gallon capacity. | 11/28/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide self locking mechanism for machine room door. | 8/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Label main line disconnect feed source, panel and breaker. 2.8 | 8/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Label 110VAC car light disconnect feed source, panel and breaker. 2.8 | 8/3/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Fire recall module in machine room missing cover. | 8/3/2022 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV valve not tested at time of inspection. Reinspection required for certificate. | 11/28/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove padlock from machine room door, and provide a self locking mechanism for machine room door. | 7/8/2024 |