Inspection
Inspection Details
Equipment ID
22634
22634
Inspection Date
7/23/2020
7/23/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wendy Eiss
Wendy Eiss
Mechanic Name
Donald Mueller
Donald Mueller
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
dbc8ba6b-c166-407c-9866-0394d7caf71f
dbc8ba6b-c166-407c-9866-0394d7caf71f
Location
West Blvd Elementry
319 W BLVD N, COLUMBIA, MO
Phone: (573) 214-3670
319 W BLVD N, COLUMBIA, MO
Phone: (573) 214-3670
Owner
Attn: Columbia Public Schools
Columbia Public Schools
5909 Paris Rd, COLUMBIA, MO 65202
Phone: (573) 214-3774
Email: KPace@cpsk12.org
Columbia Public Schools
5909 Paris Rd, COLUMBIA, MO 65202
Phone: (573) 214-3774
Email: KPace@cpsk12.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Sump pump hole needs cover. | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Sump Pump hole needs cover | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency lights out. Needs battery replaced | 7/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell not working, Battery bad | 7/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals | Yes | No | 8.6.5.5.1 Right Jack is leaking due to lack of maintenance for several months need to ascertain if jack needs to be repacked or not | 7/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Battery for emergency light and alarm needs to be changed | 8/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Please display current State Operating certificate in Elevator equipment room | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell not working. Bad battery | 6/30/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE MUST BE MADE OPERABLE | 3/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | Yes | No | MUST TEST OSV RE-INSPECTION WITH WEIGHTS REQUIRED | 3/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE MUST BE MADE OPERABLE |