Inspection
Inspection Details
Equipment ID
12010
12010
Inspection Date
7/8/2020
7/8/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
5dd5ae95-e75b-467a-9f91-6a6016dfdf9c
5dd5ae95-e75b-467a-9f91-6a6016dfdf9c
Location
Boulders at Katy Trail
262-296 SCENIC COVE LN, SAINT CHARLES, MO
Phone: (636) 477-7726
262-296 SCENIC COVE LN, SAINT CHARLES, MO
Phone: (636) 477-7726
Owner
Attn: Boulders at Katy Trail
Boulders at Katy Trail
262-296 SCENIC COVE LN, SAINT CHARLES, MO 63303
Phone: (000) 000-0000
Boulders at Katy Trail
262-296 SCENIC COVE LN, SAINT CHARLES, MO 63303
Phone: (000) 000-0000
Billing
Attn: Katy Trail Condo Association
Katy Trail Condo Association
2650 South Hanley Road, Suite 200, SAINT LOUIS, MO 63144
Phone: (000) 000-0000
Email: mandy@katytraillife.com
Katy Trail Condo Association
2650 South Hanley Road, Suite 200, SAINT LOUIS, MO 63144
Phone: (000) 000-0000
Email: mandy@katytraillife.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 7/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. Phone still not operational from May 2019 | 7/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 5/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. | 5/26/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | The A/C unit shall have a drip pan underneath it to prevent water dripping on the machine room floor. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 6/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. (2nd Notice) Re-Inspection required in 14 days. | 7/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is unsealed and shall be tested with the rated load. | 7/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate displayed is for the incorrect unit (12090). The proper state operating certificate shall be obtained and displayed. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be properly documented monthly on log sheet. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Wiring diagrams not present in machine room. | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. All three machine room locks are broken. Repair or replace. | 4/7/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not sealed or tagged and has been cited multiple times. Category 5 testing of the elevator shall be completed within 90 days or elevator will be locked out of service. | 4/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | A/C unit over tank needs drip pan to allow ?uids to ?ow away from pump unit and not on ?oor. |