Inspection
Inspection Details
Equipment ID
24832
24832
Inspection Date
7/14/2020
7/14/2020
Inspection Type
New Installation
New Installation
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
26ac1529-648c-4966-9b58-7e17e2169537
26ac1529-648c-4966-9b58-7e17e2169537
Location
Ball Park Village
One Cardinal Way, Saint Louis, MO
Phone: (770) 825-1218
Email: rbyers@asgelevators.com
One Cardinal Way, Saint Louis, MO
Phone: (770) 825-1218
Email: rbyers@asgelevators.com
Owner
Attn: Ballpark Village Holdings Block 350 LLC
Ballpark Village Holdings Block 350 LLC
601 E PRATT ST 5TH FL, BALTIMORE, MD 21202
Phone: (000) 000-0000
Email: emueller@stlballparkvillage.com
Ballpark Village Holdings Block 350 LLC
601 E PRATT ST 5TH FL, BALTIMORE, MD 21202
Phone: (000) 000-0000
Email: emueller@stlballparkvillage.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Incomplete test. Seismic testing needs completed, pull out/pull through (governor) needs to be tested, 125% overload hold needs to be tested, car safeties with full load needs to be tested, slide measurement needs to be recorded, unintended motion full load needs to be tested, and emergency power shall be tested. | 10/14/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Escape hatch switch shall be connected to the escape hatch. | 10/14/2024 |
| A17.1-2016 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | No | No | Escape hatch switch shall be connected to the escape hatch. | 12/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | These items remain - car and counterweight buffers , Governor jaw and switch trip speeds, pull out and pull thru, up unintended | 12/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Escape hatch switch to be connected to escape hatch. | 12/31/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Following testing required:1. Gov elec and jaw, record results. 2. Gov pull/through, record results., 3 seismic feature., 4 125% brake test., 5 emergency power., 6 em power selector switch. | 12/31/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Car top escape door switch not connected to door. | 1/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Seismic feature not working. | 1/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 1/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 1/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. | 9/30/2025 |