Inspection
Inspection Details
Equipment ID
22771
22771
Inspection Date
6/29/2020
6/29/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
NA
NA
Slide
1"
1"
Governor Rope Pull
30/100
30/100
Door Closing Force
NA
NA
External ID
138361cf-ed6d-4742-89c2-719e3fc6d0cf
138361cf-ed6d-4742-89c2-719e3fc6d0cf
Location
MO Baptist University - Spartan Field
1 COLLEGE PARK DR, CREVE COEUR, MO
Phone: (314) 434-1115
1 COLLEGE PARK DR, CREVE COEUR, MO
Phone: (314) 434-1115
Owner
Attn: MO Baptist University
MO Baptist University
1 COLLEGE PARK DR, SAINT LOUIS, MO 63141
Phone: (314) 744-7623
Email: Andy.Hough@mobap.edu
MO Baptist University
1 COLLEGE PARK DR, SAINT LOUIS, MO 63141
Phone: (314) 744-7623
Email: Andy.Hough@mobap.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.31 - Slack Rope Device - Roped-Hydraulic Elevators Installed Under A17.1b-1989 and Later Editions | 8.11.3.1.3(z) | No | Yes | Slack cable switch not operating. Unit Red-Tagged. | 2/15/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide code compliant maintenance records. | 12/24/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate in the machine room. | 12/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/15/2020 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | 8.6.5.5.2 - Oil leakage collected from each cylinder head seal or packing gland shall not exceed 5 gallons before removal. (The oil recovery line from the hydraulic head is presently being run directly to the tank - oil loss cannot be monitored) | 10/15/2020 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.11.3.1.2(bb) | No | No | The governor shall have a test tag installed. | 6/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.3.1.5 (j) Car Safety | No | No | A category 5 test shall be performed. | 6/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.34 - Flexible Hydraulic Hose and Fitting Assemblies | 3.19.3.3 Flexible Hydraulic Connections | Yes | Yes | A hydraulic hose in the pump unit ruptured. Elevator Red Tagged. | 11/3/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | All annual inspection items still need to be witnessed with the exception of the hoistway scan. | 11/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 9/26/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | A category 5 test shall be performed on the overspeed valve in 2025. Note: Unit is a LU/LA and may have other items that need category 5 testing. | 9/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency communications/phone still not working. Elevator Red Tagged out of service. | 10/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | A category 5 test shall be performed on the overspeed valve in 2025. Note: Unit is a LU/LA and may have other items that need category 5 testing. | 10/16/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The phone shall establish two-way communication and give location of the elevator on battery back up. |