Inspection
Inspection Details
Equipment ID
16957
16957
Inspection Date
6/19/2018
6/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
Location
Independence Center
2035 Independence Center Dr, Independence, MO
Phone: (816) 795-8602
2035 Independence Center Dr, Independence, MO
Phone: (816) 795-8602
Owner
Simon Property Group
115 W Washington, Indianapolis, IN 46204
115 W Washington, Indianapolis, IN 46204
Billing
Attn: Independence Center
2035 Independence Center Dr, , MO 64059
2035 Independence Center Dr, , MO 64059
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Right Handrail needs to be repaired or Replaced | 2/22/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 7.3 - Handrails | 8.11.4.2.13 | No | No | Handrail is broken an needs to be repaired or replaced | 6/11/2020 |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | no current cirt displayed | |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | left handrail cracked an broken | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | current. cirt. not posted | |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | left handrail cracked finger pincher needs repair or replacement | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | bottom end needs cleaned | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | maint records not current | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | no current cirt displayed | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | Escalator interior needs to be cleaned dn. | |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Left handrail needs repaired or replaced | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | no current cirt displayed | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | need internal clean dn of truss | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.13 | No | No | esc needs internal clean dn truss .tracks, pan | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.15.12 | Yes | No | esc needs Stepchains replaced bad chain rollers | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | no current cirt displayed |