Inspection
Inspection Details
Equipment ID
8598
8598
Inspection Date
7/13/2020
7/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
750
750
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
1ef10064-0d14-43c2-bac8-9ee2a802da9d
1ef10064-0d14-43c2-bac8-9ee2a802da9d
Location
Veronica House
12284 DE PAUL DR, BRIDGETON, MO
Phone: (314) 591-1660
12284 DE PAUL DR, BRIDGETON, MO
Phone: (314) 591-1660
Owner
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
Billing
Attn: The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
12284 DE PAUL DR, BRIDGETON, MO 63044-2508
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 10/4/2018 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A completed fire service testing log shall be kept on-site. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide car numbering on the controller. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide car numbering on disconnect(s). | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide car numbering on car top. | 10/9/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 10/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. | 11/4/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. | 12/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. | 9/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. (2nd Notice) | 9/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The MCP is missing. | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit must be clean and free of oil and debris. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering function shall be operational. Repair and test or apply for State variance. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually. Last tested 9/9/24. | 6/22/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Yes | No | There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Yes | No | There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance. |