Inspection
Inspection Details
Equipment ID
5187
5187
Inspection Date
8/4/2020
8/4/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Sonny Rylant
Sonny Rylant
Relief Valve Pressure
Slide
Stopped Level
Stopped Level
Governor Rope Pull
NA / NA
NA / NA
Door Closing Force
NA
NA
External ID
d3e47e7a-c93f-4b24-aa1d-5178ea5caf5c
d3e47e7a-c93f-4b24-aa1d-5178ea5caf5c
Location
Howard Thurman Building
220 E COMMERCIAL ST, SPRINGFIELD, MO
Phone: (417) 863-9044
220 E COMMERCIAL ST, SPRINGFIELD, MO
Phone: (417) 863-9044
Owner
Attn: Howard Thurman Building
Howard Thurman Building
220 E COMMERCIAL ST, SPRINGFIELD, MO 65803-2940
Howard Thurman Building
220 E COMMERCIAL ST, SPRINGFIELD, MO 65803-2940
Billing
Attn: Howard Thurman Building
2510 N FORT AVE, SPRINGFIELD, MO 65803-1136
2510 N FORT AVE, SPRINGFIELD, MO 65803-1136
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | No | No | Has pad lock hasp to aloow locking outside hoistway doors | 8/16/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Install keyed release box's for pit access to keep public from opening hoistway doors | 8/16/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | 2.2.4.1 (116.6a) Install unlocking device @ bottom landing to allow access to pit | 8/16/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Top of hoistway to be fully enclosed Code 2.1.1.2.2 | 8/16/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Metal gate be of deign to reject a ball 3'' in diamater | 8/16/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide proper access to equipment room/ Intall proper door/jambs (Code 2.7.3) | 8/16/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | Install car top stop switch ( 210.2 (h) | 11/22/2019 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | main Line disconnect required to be fused ( code 2.26.4.1--NFPA 70 ) | 8/16/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Install proper access to allow entry to elevator equipment room | 8/16/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Phone does not work | 8/4/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide Proper Access to Equipment Room/ Install steps to allow proper access to the roof leading to equipment room | 8/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light | 8/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | 2 Way communications required | 8/25/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light to be replaced | 10/7/2024 |