Inspection
Inspection Details
Equipment ID
9507
9507
Inspection Date
8/5/2020
8/5/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
520
520
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
23
23
External ID
f3073a98-bd10-4fae-bf46-010d2ca70b8a
f3073a98-bd10-4fae-bf46-010d2ca70b8a
Location
Johnson-Wabash Elementary School
685 JANUARY AVE, FERGUSON, MO
Phone: (314) 524-0280
685 JANUARY AVE, FERGUSON, MO
Phone: (314) 524-0280
Owner
Attn: Accounting
Ferguson- Florissant School District
8855 Dunn Road, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: accountspayable@fergflor.org
Ferguson- Florissant School District
8855 Dunn Road, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: accountspayable@fergflor.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 2/27/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 3/24/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log | 10/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide complete maintenance control plan and place on controller | 10/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace broken tile on floor in car | 10/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need a maintenance control program including testing procedures in the machine room | 3/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 8/15/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 3/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car | 12/6/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Test overspeed valve on or before 8/1/23 (unsealed) Pst due, 30 day maximum from date of this report to complete test | 2/25/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current State Certificate in the Machine Room | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Perform Monthly Fire Service Test and Document on the Log posted in the Machine Room |