Inspection
Inspection Details
Equipment ID
8479
8479
Inspection Date
8/7/2020
8/7/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Kevin Liles
Kevin Liles
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
22
22
External ID
e0ec17f4-2592-484f-8e20-a8d5235aaaec
e0ec17f4-2592-484f-8e20-a8d5235aaaec
Location
Boeing Bldg #100
MCDONNELL BLVD & AIRPORT RD, BERKELEY, MO
Phone: (314) 234-6485
MCDONNELL BLVD & AIRPORT RD, BERKELEY, MO
Phone: (314) 234-6485
Owner
Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Billing
Attn: Boeing Co
PO BOX 516, SAINT LOUIS, MO 63166-0516
PO BOX 516, SAINT LOUIS, MO 63166-0516
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller | 5/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | MOD acceptance test is incomplete. Only the governor section of the acceptance is complete. All other acceptance testing items shall be completed. | 3/27/2024 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | FAID failed to initiate recall. All FAID devices shall be tested. | 3/27/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | Machine room ladder shall be code compliant (currently 26" floor to first rung and less than required 4.5" from wall). | 3/27/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevator will have the capability to operate on emergency power, but it was not operational at time of the MOD. Emergency power operation shall be tested once MOD is completed. | 3/27/2024 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | Yes | No | Machine room ladder shall be code compliant (currently 26") floor to first rung and less than required 4.5" from wall. | 4/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevator will have the capability to operate on emergency power, but it was not operational at time of the MOD. Emergency power operation shall be tested once MOD is completed. | 4/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevator will have the capability to operate on emergency power, but it was not operational at time of the MOD. Emergency power operation shall be tested once MOD is completed. | 5/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | This annual inspection was not completed. The only test perfomed were unintended motion and soft set of safties (both compliant). All other annual testing shall be completed. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | All automatic passenger elevators with power doors shall have reopening devices on the doors, designed to reopen doors in the event the door should become obstructed. The electronic eye/light curtain failed to detect obstruction and reopen doors. |