Inspection
Inspection Details
Equipment ID
14082
14082
Inspection Date
8/3/2020
8/3/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
6e17470a-87bd-4984-a278-202bb72dcae9
6e17470a-87bd-4984-a278-202bb72dcae9
Location
Fire House #2
11804 BIG BEND RD, KIRKWOOD, MO
Phone: (314) 822-5883
11804 BIG BEND RD, KIRKWOOD, MO
Phone: (314) 822-5883
Owner
Kirkwood, City of
139 S KIRKWOOD RD, KIRKWOOD, MO 63122-4303
139 S KIRKWOOD RD, KIRKWOOD, MO 63122-4303
Billing
Attn: Kirkwood, City of
212 S TAYLOR AVE, KIRKWOOD, MO 63122-4325
212 S TAYLOR AVE, KIRKWOOD, MO 63122-4325
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/13/2019 |
| A17.1-1996 : Elevators | 3.5 - Normal terminal stopping device | 1002.2e | Yes | No | Car shall stop in the down direction while on car top inspection prior to striking the buffer. When the car strikes the buffer, it activates the low pressure switch, rendering the car inoperable. | 11/13/2019 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 1001.2(b)(11) | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 11/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/22/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 11/22/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 11/22/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The annual inspection was not completed. The following items shall be tested: Relief pressure, pressure switch, low oil timer. | 8/4/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 full load test shall be performed on the overspeed valve in 2022. | 9/2/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP, including PM records and monthly fire service test log are not being properly documented. | 2/14/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 2/14/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall work. Take corrective action as needed. | 8/28/2023 |