Inspection
Inspection Details
Equipment ID
13727
13727
Inspection Date
7/27/2020
7/27/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
32
32
Governor Rope Pull
150/1100
150/1100
Door Closing Force
NA
NA
External ID
6dd6e0c1-6de2-47cc-a27f-72cbd83d2810
6dd6e0c1-6de2-47cc-a27f-72cbd83d2810
Location
AT & T - One Bell Center
1010 PINE ST, SAINT LOUIS, MO
Phone: (314) 396-3759
1010 PINE ST, SAINT LOUIS, MO
Phone: (314) 396-3759
Owner
Attn: Kenneth Gerry
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@us.att.net
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@us.att.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Provide Emergency Phone | 3/29/2019 | |
A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | x | Interlock cover on the 17th floor missing. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 2/24/2021 | |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | x | Overspeed governor rope tension sheave is bottomed out. Shorten governor rope. Red tagged. | 2/24/2021 |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/2/2022 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace missing tactile plate on COP | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Replace CO2 fire extinguishers with ABC type. Both elevator machine room and secondary spaces. | |||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Provide existing emergency lights and bell to work. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing pull straps (3), floors 2B,S,1.. hoistway doors. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Provide testing of the elevator on emergency power. | ||
A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | x | Provide testing of the elevator emergency power selector switch (fire command room). |