Inspection
Inspection Details
Equipment ID
15019
15019
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
Location
Oak Street Housing
5051 Oak Street, Kansas City, MO
Phone: (816) 235-1363
5051 Oak Street, Kansas City, MO
Phone: (816) 235-1363
Owner
UMKC
1011 East 51st St, Gen Services Bldg, Kansas City, MO 64110
1011 East 51st St, Gen Services Bldg, Kansas City, MO 64110
Billing
Attn: UMKC- Campus Facilities Mgmt
1011 East 51st St, Gen Services Bldg, , MO 64110
1011 East 51st St, Gen Services Bldg, , MO 64110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.11.3.1.1(h) | Yes | No | adjust the door close force to below 30 lbs, the doors maxed out my gauge (2.13.4.2.3) | 6/16/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | repair and adjusted door restrictor, it is not working | 6/3/2024 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | replace first floor hoistway door astragal, it is no longer glued to the bottom half of the door | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | clean up the oil on the pit floor | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | repair machine room air conditioner so it works | |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Repair and adjust door restrictor, it is not working | 8/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil from the pit |