Inspection
Inspection Details
Equipment ID
15020
15020
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
Location
Oak Street Housing
5051 Oak Street, Kansas City, MO
Phone: (816) 235-1363
5051 Oak Street, Kansas City, MO
Phone: (816) 235-1363
Owner
UMKC
1011 East 51st St, Gen Services Bldg, Kansas City, MO 64110
1011 East 51st St, Gen Services Bldg, Kansas City, MO 64110
Billing
Attn: UMKC- Campus Facilities Mgmt
1011 East 51st St, Gen Services Bldg, , MO 64110
1011 East 51st St, Gen Services Bldg, , MO 64110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | elevator shutdown during the inspection, test was not completed, need to schedule reinspection | 8/16/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.11.3.1.1(h) | Yes | No | the door close force is right at the maximum, recommend adjusting it so the force is below 30 lbf. (A17.1-2016 [2.13.4.2.3]) force shall not exceed 30 lbf | 6/16/2023 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | emergency lights did not come on, suspect that the emergency light battery is dead, replace battery | 6/16/2023 |
| A17.1-2016 : Elevators | 2.39 - Low Oil Protection | 8.6.5.12 | No | No | low on oil, cavitates at the top landing (A17.1-2016 [3.24.2]) adequate liquid reserve in order to prevent the entrance of air into the system. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | repair and adjust door restrictor, it is not working | 6/3/2024 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Repair and adjust door restrictor, it is not working | 8/30/2024 |