Inspection
Inspection Details
Equipment ID
22683
22683
Inspection Date
7/29/2020
7/29/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
94735b9f-2ee6-4a09-9d21-0ab3331c538b
94735b9f-2ee6-4a09-9d21-0ab3331c538b
Location
Whole Foods
4577 West Pine Blvd, SAINT LOUIS, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
4577 West Pine Blvd, SAINT LOUIS, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
Owner
Attn: Whole Foods
Whole Foods
4577 West Pine, SAINT LOUIS, MO 63108
Phone: (314) 474-7300
Email: mwcwestoreleadership@wholefoods.com
Whole Foods
4577 West Pine, SAINT LOUIS, MO 63108
Phone: (314) 474-7300
Email: mwcwestoreleadership@wholefoods.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19.4.1 | Repair supply line leak at valve to jack side threaded connection. | 9/15/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Reprogram cab hands free phone. Current program lists former Euclid address/owner | 7/29/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside elevator equipment room. | 9/15/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Provide self-locking lock on machine room door. | 9/15/2025 | ||
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display operating Missouri operating certificate in machine room | 9/15/2025 | ||
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Door restrictor inoperable reinspect in 30 days. Repair or replace | 5/8/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency communication inoperable when elevator power is turned off. Phone works on emergency power | 5/8/2024 | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Car door restrictor does not work, needs repaired. Re-inspection required | 11/1/2024 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Elevator cab phone does not work, phone line has no power. Re-inspection required | 11/1/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | 9/15/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | 9/15/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Car door restrictor does not work, needs repaired. Re-inspection required | 12/30/2024 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 9/15/2025 |