Inspection
Inspection Details
Equipment ID
18526
18526
Inspection Date
8/6/2020
8/6/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
e277bc7d-6d15-4421-ab5f-cd2b52c84711
e277bc7d-6d15-4421-ab5f-cd2b52c84711
Location
Arlington Apartments
800 ARLINGTON AVE, SAINT LOUIS, MO
Phone: (000) 000-0000
800 ARLINGTON AVE, SAINT LOUIS, MO
Phone: (000) 000-0000
Owner
Attn: So Lofts
So Lofts
1224 Washington Ave, SAINT LOUIS, MO 63112
Phone: (314) 367-7646
So Lofts
1224 Washington Ave, SAINT LOUIS, MO 63112
Phone: (314) 367-7646
Billing
Attn: So Lofts
So Lofts
1224 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 367-7646
So Lofts
1224 Washington Ave, SAINT LOUIS, MO 63103
Phone: (314) 367-7646
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | Make supply line shutoff valve operational. | 1/18/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 1/18/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency lights shall be operational. | 8/6/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The alarm bell shall be operational. | 8/6/2020 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 9/9/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up-to-date operating certificate is required in the machine room. | 9/26/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/24/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Auxiliary power lowering operation shall work. | 9/24/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump is not allowed in pit as amount of oil leakage cannot be determined. | 8/24/2024 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | The car top lighting shall be operational. | 8/24/2024 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Remove materials that are blocking access to the machine room. | 7/17/2025 |