Inspection
Inspection Details
Equipment ID
13196
13196
Inspection Date
8/12/2020
8/12/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
330
330
Slide
Governor Rope Pull
Door Closing Force
20/20
20/20
External ID
f0c65a8c-6f94-4c13-9c70-23c7890faa62
f0c65a8c-6f94-4c13-9c70-23c7890faa62
Location
Saint Francis Medical Center
211 SAINT FRANCIS DR, CAPE GIRARDEAU, MO
Phone: (000) 000-0000
211 SAINT FRANCIS DR, CAPE GIRARDEAU, MO
Phone: (000) 000-0000
Owner
Attn: Mark Culberson
St. Francis Medical Center
211 SAINT FRANCIS DR, CAPE GIRARDEAU, MO 63703
Phone: (573) 331-5200
Email: bpierce@sfmc.net
St. Francis Medical Center
211 SAINT FRANCIS DR, CAPE GIRARDEAU, MO 63703
Phone: (573) 331-5200
Email: bpierce@sfmc.net
Billing
Same as Owner