Inspection
Inspection Details
Equipment ID
5821
5821
Inspection Date
7/29/2020
7/29/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Drinkard
Dennis Drinkard
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
495
495
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
02a5f44e-66a3-4e6e-a04a-97f9db2a1512
02a5f44e-66a3-4e6e-a04a-97f9db2a1512
Location
Truman High School
3301 S NOLAND RD, INDEPENDENCE, MO
Phone: (816) 521-2710
3301 S NOLAND RD, INDEPENDENCE, MO
Phone: (816) 521-2710
Owner
Attn: Geri Frink
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | either replace the drop ceiling panels or install covers on the light tubes to prevent breakage | 5/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | replace missing jamb braille | 5/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | provide fire extinguisher with updated inspection tag, the one that is in the machine room has an expired inspection tag | 5/20/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | the fire service phase 2 operating instructions do not match the operation of the elevator, provide sign with the correct operating instructions | 3/12/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to perform and post monthly fire service test log in the elevator machine room | 5/20/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | instal covers on cab light tubes so they are guarded to prevent breakage | 5/20/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | update firefighters'service operation monthly test results | 12/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | provide a ABC fire extinguisher convenient to the access door | 12/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | replace missing hoistway jamb braille tag at 2nd floor | 12/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | The firefighters service test log is not being filled out monthly. | 1/3/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Adjust the door restrictor so it works | 7/31/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not being filled out monthly | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency lights did not come on, alarm bell worked on battery power | 7/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | does not have Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | Yes | No | settled 2 inches during set test, didn't move with the gate valve close, repair or replace control valve | 7/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | fire service phase 2 instruction sign can no longer be read, provide fire service phase 2 instruction sign that matches the operation of this elevator (2.27.7.2) | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, provide working phone line | 7/31/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Adjust door restrictor so it works properly | 10/27/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Adjust door restrictor so it works properly | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | 8 inches of water in the pit, provide means to prevent the accumulation of groundwater in the pit |