Inspection
Inspection Details
Equipment ID
12482
12482
Inspection Date
8/17/2020
8/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Scott Fischer
Scott Fischer
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
ae97a23c-5bd5-443c-bfd4-04c7db02d63a
ae97a23c-5bd5-443c-bfd4-04c7db02d63a
Location
Villa Dorado Condo
11845 CRESTA VERDE DR, SAINT LOUIS, MO
Phone: (636) 733-9021
11845 CRESTA VERDE DR, SAINT LOUIS, MO
Phone: (636) 733-9021
Owner
Attn: Grier
Grier Management Group
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017
Phone: (636) 733-9021
Email: accounting@griergroupinc.com
Grier Management Group
1400 ELBRIDGE PAYNE RD STE 210, CHESTERFIELD, MO 63017
Phone: (636) 733-9021
Email: accounting@griergroupinc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Machine room door has no self-closing, self-locking feature. | 10/2/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit light inoperative. | 10/2/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door must be self closing and lockable. | 10/2/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/2/2022 | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light shall work | 10/2/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | 10/2/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car unable to provide location, needs to be upgraded to do so. Re-inspection required | 8/17/2023 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 10/2/2025 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Provide machine room door to be self closing and self locking. | 10/2/2025 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works, but unable to communicate (bad number). Reprogram phone. | 10/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Fire extinguisher in machine room is expired, replace or have serviced | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone works, but unable to communicate (bad number). Reprogram phone. Re-inspection required |