Inspection
Inspection Details
Equipment ID
10426
10426
Inspection Date
8/21/2020
8/21/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Bradley Tramel
Bradley Tramel
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
10/10
10/10
External ID
3b7296bd-6f47-40d6-a814-ecf3749f5658
3b7296bd-6f47-40d6-a814-ecf3749f5658
Location
Mercy Hospital South
10010 KENNERLY RD, SAINT LOUIS, MO
Phone: (618) 979-3219
10010 KENNERLY RD, SAINT LOUIS, MO
Phone: (618) 979-3219
Owner
Attn: UNK
Mercy Hospital South
10010 KENNERLY RD, SAINT LOUIS, MO 63128
Phone: (314) 525-1194
Email: Jerry.White2@Mercy.net
Mercy Hospital South
10010 KENNERLY RD, SAINT LOUIS, MO 63128
Phone: (314) 525-1194
Email: Jerry.White2@Mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | The elevator pit shall be cleaned of dust and debris. | 7/17/2019 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 10/20/2020 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required. | 7/13/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit to remove debris, water, and/or oil and address sources. | 11/22/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | The elevator controller has a temporary jumper in use for a resistor that has failed. Repair controller and remove the temporary jumper. | 7/23/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required. | 1/31/2024 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 1001.2(d)(2) | No | No | 8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs. | 7/23/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 7/23/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 1001.2(d)(2) | No | No | 8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs. | 7/23/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator and fire service testing shall be done. Scheduled 8/19/25 | 8/19/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. This is the 4th year that this violation has been issued. A permanent means SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance. |