Inspection
Inspection Details
Equipment ID
11905
11905
Inspection Date
8/14/2020
8/14/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
11905
11905
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
22
22
External ID
3ccb4eec-23d3-43e3-98db-79ad308d9d28
3ccb4eec-23d3-43e3-98db-79ad308d9d28
Location
AmeriStar Casino
1 AMERISTAR BLVD, SAINT CHARLES, MO
Phone: (636) 940-4340
1 AMERISTAR BLVD, SAINT CHARLES, MO
Phone: (636) 940-4340
Owner
Attn: UNK
AmeriStar Casino- St. Charles LLC
1260 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
AmeriStar Casino- St. Charles LLC
1260 S MAIN ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Billing
Attn: AmeriStar Casino- St. Charles, LLC
AmeriStar Casino- St. Charles LLC
1 AMERISTAR BLVD, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
AmeriStar Casino- St. Charles LLC
1 AMERISTAR BLVD, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: patmcdonald@boydgaming.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current certificate on display. | 7/17/2019 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Replace top floor door restrictor bracket. | 7/2/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV must have a cat 5 weight test performed within 90 days or less | 9/22/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Monthly firefighters service logs shall be maintained on site | 5/25/2022 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | Doors need to have stenciling labeling correct floor | 5/25/2022 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Top floor is missing a door gib | 5/25/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Fill hole in hoistway making hoistway completely enclosed | 5/25/2022 |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | Yes | Yes | Suspension ropes are undersized with rouge. RED TAGGED | 9/22/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | Yes | No | OSV needs to be tested with full load within 90 days | 9/22/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Yes | No | Monthly firefighters logs shall be maintained on site | 9/22/2021 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Yes | No | Top floor door is missing door gib | 9/22/2021 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | Yes | No | Door needs to have stenciling labeling of correct floor | 9/22/2021 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | Yes | No | Fill hole in hoistway making hoistway fully closed | 9/22/2021 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV is not sealed and must have a cat 5 weight test performed within 90 days or less | 3/25/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Monthly firefighters service logs shall be maintained on site | 3/25/2022 |
| A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) | No | No | Fill hole in hoistway making hoistway completely enclosed | 3/25/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety/code concern. Without motion, the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch. | 8/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | The hoistway door at the 3rd landing is not self-closing/self-locking. The hoistway door shall be adjusted. | 8/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A door retaining gib is missing on the 2nd floor hoistway door, a replacement door gib shall be installed. | 8/9/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate shall be posted in the machine room in a non-combustible frame. | 8/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The hoistway door at the 3rd landing is not self-closing/ self-locking. The hoistway door shall be adjusted. | 8/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | A door retaining gib is missing on the 2nd floor hoistway door, a replacement door gib shall be installed. | 8/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate shall be posted in the machine room in a non-combustible frame. | 8/23/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room. | 8/22/2023 |