MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
8/24/2020
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements.
|
8/11/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/16/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is expired.
|
12/27/2023
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone is not working. It dials out, but no one answers.
|
11/20/2023
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
x
|
Ropes shall be shortened to allow activation of top final before full counterweight buffer compression, resulting in loss of traction. Elevator Red Tagged.
|
8/6/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit.
|
8/6/2024
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking.
|
9/25/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
COP shall have car number displayed (multiple units onsite).
|
9/25/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Detector edge shall work with cab lighting off. Door safety circuit cannot be wired to a lighting circuit. Note: Elevator is about to undergo modernization and violation to be corrected at that time.
|
9/25/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency power needs to be tested.
|
9/25/2025
|