Inspection
Inspection Details
Equipment ID
13611
13611
Inspection Date
8/13/2020
8/13/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
5eced5ba-cf93-44fd-8732-92a606688f6d
5eced5ba-cf93-44fd-8732-92a606688f6d
Location
5393 Nagel Apartments
5939 NAGEL AVE, SAINT LOUIS, MO
Phone: (314) 752-4863
5939 NAGEL AVE, SAINT LOUIS, MO
Phone: (314) 752-4863
Owner
Allegro
CLAYTON RD, RICHMOUND HEIGHTS, MO 63117
CLAYTON RD, RICHMOUND HEIGHTS, MO 63117
Billing
Attn: Allegro
1140 LAY RD, SAINT LOUIS, MO 63124-1851
1140 LAY RD, SAINT LOUIS, MO 63124-1851
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Water in pit. | 11/2/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Provide a written maintenance control program. 8.6.1.2.1 | 11/2/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Counterweight buffer stand is rusted out and not secured. Replace deteriorated buffer stand within 15 days or unit will be removed from service. | 10/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace seized up counterweight rollers. | 10/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide written maintenance control program. | 10/19/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program is required. | 10/19/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties with rated load at rated speed. Re-inspection required | 6/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test car safeties with rated load at rated speed. Re-inspection required | 10/7/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Full load test has not been completed. Need to test car safeties with rated load at rated speed within 30 days or elevator will be red-tagged and removed from service. Re-inspection required | 10/23/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current state operating certificate shall be displayed in elevator machine room. | 7/2/2026 |