Inspection
Inspection Details
Equipment ID
14140
14140
Inspection Date
6/19/2018
6/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
25"
25"
Governor Rope Pull
250/950
250/950
Door Closing Force
25
25
External ID
Location
Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2768
1465 S Grand Blvd, St. Louis, MO
Phone: (314) 268-2768
Owner
SSM-Cardinal Glennon Childrens Hospital
1465 S Grand Blvd, St. Louis, MO 63104
1465 S Grand Blvd, St. Louis, MO 63104
Billing
Attn: SSM-Cardinal Glennon Childrens Hospital
P O Box 410830, , MO 63141
P O Box 410830, , MO 63141
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 201 | Yes | No | The car buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. | 9/12/2022 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 201 | Yes | No | The counterweight buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. | 7/7/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 7/7/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test elevator on phase I & II fire service. Re-inspection required | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Elevator machine room has multiple light bulbs that do not work, needs repaired | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, need repaired. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. |