Inspection
Inspection Details
Equipment ID
7043
7043
Inspection Date
8/25/2020
8/25/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Oscar Yanez, Jr.
Oscar Yanez, Jr.
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
0ac51af8-56c7-4f0c-bc5c-5652da1928fb
0ac51af8-56c7-4f0c-bc5c-5652da1928fb
Location
Water Department
1852 BURLINGTON ST, N KANSAS CITY, MO
Phone: (816) 274-6022
1852 BURLINGTON ST, N KANSAS CITY, MO
Phone: (816) 274-6022
Owner
Attn: City of N Kansas City
City of N Kansas City
2010 HOWELL ST, N KANSAS CITY, MO 64116
Phone: (816) 274-6004
Email: vlressler@nkc.org
City of N Kansas City
2010 HOWELL ST, N KANSAS CITY, MO 64116
Phone: (816) 274-6004
Email: vlressler@nkc.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | machine room fire extinguisher inspection tag is expired, need to get updated inspection on fire extinguisher | 6/21/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone in the elevator is not working, phone line is dead. provide working phone line to the elevator controller | 8/25/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 6/1/2021 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.3.1.3(m) | No | No | junction box missing cover in the hoistway between middle and top floor. | 9/28/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | monthly fire service test log is not being filled out | 9/28/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 9/28/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency phone is not working, phone line is dead | 8/15/2022 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | the pit bucket is upside down, oil line is not in the bucket | 9/28/2023 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.11.3.1.4(b) | Yes | No | one of the pull straps is missing on the middle landing hoistway door | 8/15/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, phone line is dead, provide a working phone line | 6/22/2023 |
| A17.1-1996 : Elevators | 4.2 - Hoistway doors | 110 | No | No | missing pull straps on hoistway doors, landing #1 both sides of door, landing #B outside pull strap (110.12h) | 9/28/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Does not have oil collection bucket in the pit, provide oil collection bucket | 2/12/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in the pit, provide means to prevent the accumulation of water in the pit. Pumped water out, attached sump pump didn’t work | 2/12/2025 |