Inspection
Inspection Details
Equipment ID
9328
9328
Inspection Date
7/17/2020
7/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Roy Parker
Roy Parker
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
4be9b24d-7d0d-494e-8de6-c9a23b9b4742
4be9b24d-7d0d-494e-8de6-c9a23b9b4742
Location
Roosevelt High School
3230 HARTFORD ST, SAINT LOUIS, MO
Phone: (314) 633-9103
3230 HARTFORD ST, SAINT LOUIS, MO
Phone: (314) 633-9103
Owner
Attn: UNK
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: cindy@advancedelevator-stl.com
Billing
Attn: Cindy Williams
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: Rosmon.Johnson@slps.org
Advance Elevator
PO BOX 423, CHILLICOTHE, MO 64601
Phone: (314) 581-0223
Email: Rosmon.Johnson@slps.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Securely mount rectifier board in the controller. | 9/23/2020 |
| conversion | conversion | n/a | No | No | Existing emergency light shall have 2 working bulbs. | 9/23/2020 |
| conversion | conversion | n/a | No | No | The tile floor in the elevator car is damaged and creates a tripping hazard. Repair the car flooring. | 9/23/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency lights shall work. | 9/23/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be operational. | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Electrical prints shall be provided in the elevator machine room. | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance records shall be kept on-site in the machine room. | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/7/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Elevator machine room not to be used for storage of cleaning gear. Remove all non elevator related items from the elevator machine room. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work correctly. | 12/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | Yes | No | Cab floor damaged, repair/replace as needed. | 12/13/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Back wall hand rail missing, replace as needed. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair or replace cab floor-tripping hazard | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Cleaning gear not allowed to be stored in the machine room. Remove all non-elevator related items from the elevator machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair or replace cab floor - tripping hazard | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Cleaning materials are not allowed to be stored in machine room. Remove all non elevator related items from the elevator machine room | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair or replace cab floor-tripping hazard. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Remove all the non elevator related items from the elevator machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide machine room to to be self locking. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Car hand rails are loose, repair as needed. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide pit light to work. |