Inspection
Inspection Details
Equipment ID
17439
17439
Inspection Date
8/19/2020
8/19/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
660
660
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
de9a64a2-38ac-41c5-aef6-d6161c91f8a1
de9a64a2-38ac-41c5-aef6-d6161c91f8a1
Location
Parrish Lofts Linen Lofts
3124 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 565-7456
3124 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 565-7456
Owner
Rafco Properties
7700 FORSYTH BLVD STE 1030, CLAYTON, MO 63105-1821
7700 FORSYTH BLVD STE 1030, CLAYTON, MO 63105-1821
Billing
Attn: Rafco Properties
7700 FORSYTH BLVD STE 1030, CLAYTON, MO 63105-1821
7700 FORSYTH BLVD STE 1030, CLAYTON, MO 63105-1821
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept dry. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be obtained and posted in the elevator machine room. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | A current tested, ABC type fire extinguisher shall be provided in the elevator machine room. | |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | The car top lighting shall be operational. | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 10/8/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit lighting shall be operational. | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Code compliant maintenance documents shall be kept on-site and shall be readily accessible. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Water and oil shall not be allowed to accumulate on pit floors. Note: The pit currently has about one foot of water in it. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit lighting shall be operational. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The missing pickup roller at the top landing shall be replaced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 100 lx (10 fc). Note: There are no working lights in the hallway at the bottom landing. |