Inspection
Inspection Details
Equipment ID
3353
3353
Inspection Date
8/24/2020
8/24/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Brent Bonham
Brent Bonham
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24/26
24/26
External ID
81372e1e-c72a-44ac-8aef-256de8f012e5
81372e1e-c72a-44ac-8aef-256de8f012e5
Location
Curry Library
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
Owner
Attn: Stephany Guest
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Test and log firefighter operation monthly | 4/21/2021 | ||
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions next to hall fire keyswitch and on car operating panel. | 4/21/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Post emergency evacuation of passengers form inside machine room. | 4/21/2021 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pits need to be kept dry | 4/21/2021 | ||
MO Minimum : Elevators | (I) - Pits | (I)2 | Counterweight buffer and pit channel rusted. Need replacement and permanent mounting of same. | 4/21/2021 | ||
MO Minimum : Elevators | (I) - Pits | (I)2 | Car buffer pit channel rusted out. Need to replace pit channel that car buffer is mounted on. | 4/21/2021 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate inside machine room. | 4/21/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Test and log firefighter operation monthly | |||
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions next to hall fire keyswitch | |||
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions next to fire keyswitch on car operating panel | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No MCP | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No maintenance records | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No fire extinguisher in machine room | |||
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions on car operating panel | |||
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions next to hall fire keyswitch | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Post In Case of Fire signage next to hall button fixture at each landing | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency bell does not operate | 8/8/2023 | |
MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post firefighter operating instructions on car operating panel and next to hall fire keyswitch | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Post In Case of Fire signage next to hall button fixture at each landing | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide type ABC fire extinguisher inside the machine room | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Front doors do not close under power during fire recall | 10/24/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | During phase 2 operation the rear doors reopen after they are fully closed and the door close button is released | 10/24/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | No fire alarm initiating devices located in the elevator lobbies or in the machine room | 10/24/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone on car operating panel does not operate. | 10/24/2024 | |
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Test and log firefighter operation monthly | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | State operating certificate not displayed | |||
MO Minimum : Elevators | (I) - Pits | (I)5 | Pit ladder rusted at bottom of ladder. Repair or replace ladder and resecure to wall. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Provide smoke detectors at each lobby, and machine room and test. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone dialing wrong number. Reprogram and retest. |