Inspection
Inspection Details
Equipment ID
19265
19265
Inspection Date
8/19/2020
8/19/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Todd Davis
Todd Davis
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
9fd6953e-a3d0-437a-9126-4b2591bb2d3e
9fd6953e-a3d0-437a-9126-4b2591bb2d3e
Location
Pottery Barn Kids
1745 S LINDBERGH BLVD, SAINT LOUIS, MO
Phone: (314) 729-2400
1745 S LINDBERGH BLVD, SAINT LOUIS, MO
Phone: (314) 729-2400
Owner
Attn: Unk
William Sonoma
3250 VAN NESS AVE, SAN FRANCISCO, CA 94109
Phone: (000) 000-0000
William Sonoma
3250 VAN NESS AVE, SAN FRANCISCO, CA 94109
Phone: (000) 000-0000
Billing
Attn: William sonoma
William Sonoma
3250 VAN NESS AVE, SAN FRANCISCO, CA 94109
Phone: (000) 000-0000
William Sonoma
3250 VAN NESS AVE, SAN FRANCISCO, CA 94109
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Car emergency telephone shall work. | 9/17/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 4/20/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/13/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 7/3/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | The door close button shall be operational on Phase 2 fire service. | 10/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | The audible signal shall work on Phase 2 fire service. | 10/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | Emergency battery lowering shall be operational. | 10/4/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 7/3/2023 |
| A17.1-2016 : Elevators | 1.7 - Car door or gate | 8.6.4.13.1 Door Systems General | No | No | Need to replace broken car door upthrust device on leading edge of car door. | 4/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 4/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram the emergency phone |