Inspection
Inspection Details
Equipment ID
10006
10006
Inspection Date
8/25/2020
8/25/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
24/26
24/26
External ID
f9d50a3f-5885-48f4-ab11-f95fffbe9eea
f9d50a3f-5885-48f4-ab11-f95fffbe9eea
Location
Student Union
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
Owner
Attn: Stephany Guest
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need to post fire service instuctions in hall by Phase 1 keyswitch. | 4/21/2021 |
| conversion | conversion | n/a | No | No | Emergency light does not function | 4/21/2021 |
| conversion | conversion | n/a | No | No | Star braille plate on car operating panel needs to be on G not 1. G is the main fire designated landing. | 4/21/2021 |
| conversion | conversion | n/a | No | No | elevator phone does not function. | 4/21/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate. | 1/21/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | Yes | Need to post fire service instructions by phase 1 keyswitch in hall. | 1/21/2019 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Braille plate for G button in car operating station needs to have a star by it to designate that G is the main fire landing. | 4/21/2021 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | Post code data plate on controller or mainline disconnect | 4/21/2021 |
| A17.1-1996 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 211.9 | No | No | Number the controller and power unit for identification. | 4/14/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 4/21/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Post emergency evacuation of passengers form inside machine room | 4/21/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 4/21/2021 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 100.7 | No | No | Number inside of hoistway doors for identification | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictors have been disabled | 1/27/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | All elevators in the same building shall use the same key for firefighter operation | 8/9/2022 |
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 210.1d | No | No | Top of car inspection station will not run the elevator in the up direction | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Test and log firefighter operation monthly | |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 1001.2(c)(15) | No | No | Identify the inside of hoistway doors with a numeral corresponding to the landing floor | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 1000.1b(3)(b) Metal Test Tag | No | No | Install metal test tag for periodic pressure relief test | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall operation | 8/9/2022 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | Car button numerals do not correspond with car postion indicator on car operating panel. | |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire service phase 1 recall. Fire hat on car operating panel and at main landing do not illuminate | 8/8/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 8/8/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.3a(8) Visual and audible signal | Yes | No | Fire hat inside and outside the elevator do not illuminate during fire recall. | 8/13/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate. Batttery needs to be replaced | 8/13/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Car position indicator needs repair so that the position indicator readout corresponds to the floor landing designations. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed |