Inspection
Inspection Details
Equipment ID
24485
24485
Inspection Date
8/21/2020
8/21/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
James Stabler
James Stabler
Relief Valve Pressure
1300
1300
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
10
10
External ID
a5b60403-a327-4cd8-b281-11b20ac5924e
a5b60403-a327-4cd8-b281-11b20ac5924e
Location
Windsor High School
949 Windsor Harbor Road, Imperial, MO
Phone: (000) 000-0000
949 Windsor Harbor Road, Imperial, MO
Phone: (000) 000-0000
Owner
Attn: Windsor C-1 School District
Windsor C-1 School District
6208 US HIGHWAY 61 67, IMPERIAL, MO 63052
Phone: (636) 464-4461
Email: mmueller@windsor.k12.mo.us
Windsor C-1 School District
6208 US HIGHWAY 61 67, IMPERIAL, MO 63052
Phone: (636) 464-4461
Email: mmueller@windsor.k12.mo.us
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide phone line for emergency two-way communication. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.3 | x | Install fire rated door on the elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | x | Change receptacles in machine room to GFIC | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | x | Install fire extinguisher in elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Install shunt trip disconnect in the elevator machine room. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.13.1 | x | Install floor covering and handrail in elevator cab. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.3.4 | x | x | Install smoke detectors for fire recall and program. | 7/12/2019 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.26.2.7 | x | Install single 110v receptacle in pit for sump pump. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | x | Install car buffers or bumpers. | 7/12/2019 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 8/26/2019 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Test incomplete due to roller broke on sling. Need to perform the following tests to complete inspection: Test safeties, phone, emergency lights & bell, OSV, cartop, & door restrictor. Re-inspection required | 3/31/2025 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Inspection incomplete. The OSV still needs to be tested. The elevator quit running during inspection |