Inspection
Inspection Details
Equipment ID
9862
9862
Inspection Date
8/25/2020
8/25/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
Na
Na
Door Closing Force
26
26
External ID
504caf62-b0ea-4b1e-954a-4cdf3f3cfccc
504caf62-b0ea-4b1e-954a-4cdf3f3cfccc
Location
One Financial Plaza
501 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 588-7171
501 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 588-7171
Owner
Attn: One Financial Plaza/Cushman & Wakefield
One Financial Plaza/Cushman & Wakefield
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102
Phone: (314) 588-7171
Email: lea.jackson@cushwake.com
One Financial Plaza/Cushman & Wakefield
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102
Phone: (314) 588-7171
Email: lea.jackson@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | No | No | Replace bottom left counterweight roller guides. | 2/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher is out of date. | 2/20/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Rope gauge bottoms on #5 hoist rope between floors 10-11. Replace hoist ropes within 60 days from above date. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace deteriorating under car safety assembly bushings. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Counterweight safety tension sheave nearing bottom of travel, raise sheave. | 1/9/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace first floor interlock box cover. | 1/9/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Provide data tag for recent suspension rope replacement on machine room hitch plate. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace under car safety assembly bushings. | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 2/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 4/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 4/1/2026 |