Inspection
Inspection Details
Equipment ID
19071
19071
Inspection Date
8/20/2020
8/20/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
26/22
26/22
External ID
655c9564-55aa-46e8-9b81-3b95d8721e8a
655c9564-55aa-46e8-9b81-3b95d8721e8a
Location
Ludwig Lofts
1006 OLIVE ST, SAINT LOUIS, MO
Phone: (512) 350-3990
1006 OLIVE ST, SAINT LOUIS, MO
Phone: (512) 350-3990
Owner
Attn: UNK
Ludwig Investments
1006 OLIVE ST, SAINT LOUIS, MO 63101
Phone: (512) 350-3990
Ludwig Investments
1006 OLIVE ST, SAINT LOUIS, MO 63101
Phone: (512) 350-3990
Billing
Attn: UNK
Ludwig Investments
231 S Bemistion, Ste 850 #94195, SAINT LOUIS, MO 63105
Phone: (512) 350-3990
Email: tara@needwant.com
Ludwig Investments
231 S Bemistion, Ste 850 #94195, SAINT LOUIS, MO 63105
Phone: (512) 350-3990
Email: tara@needwant.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 111.7 | No | No | Hoistway access does not work. | 6/1/2022 |
| A17.1-1996 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 1001.2(e)(2) | Yes | No | Ropes exceed maximum runby of 6 inches. | 8/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.6 | No | No | Access to hoistway does not work. | 6/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | Ropes exceed maximum runby of 6 inches. | 11/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No maintenance control program on site. | 6/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 3/18/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab is not working. Re-inspection required | 4/11/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | MCP needs to include procedures for inspections & tests | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Records of maintenance, trouble calls, repairs, etc needs to be filled out | 8/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No | No | Hoistway access key switches are not working | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Two bulbs are required in car lighting fixture. Replace bad and/or missing bulbs | 8/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator items from the elevator machine room. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work properly. | 8/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Provide hoistway access switches to work. | 8/12/2026 |