Inspection
Inspection Details
Equipment ID
2612
2612
Inspection Date
9/1/2020
9/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jeffrey VanZant
Jeffrey VanZant
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
6c4470c6-4699-49de-9f74-158420f44d7c
6c4470c6-4699-49de-9f74-158420f44d7c
Location
Crowder College- Neosho
601 LACLEDE AVE, NEOSHO, MO
Phone: (417) 455-5544
601 LACLEDE AVE, NEOSHO, MO
Phone: (417) 455-5544
Owner
Attn: Crpwder
Crowder College- Neosho
601 LACLEDE AVE, NEOSHO, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Crowder College- Neosho
601 LACLEDE AVE, NEOSHO, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | telephone will not call out | 7/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Machine Room Ceiling panels need to be replaced (2nd violation: 2019 and 2020) | 4/27/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Resecure machine room smoke detector to ceiling (2nd violation: 2019 and 2020) | 7/12/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Detector edge shall work independent of cab lighting circuit (reinspection needed) | 4/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit Scavenger pump shall be removed. Reinspection needed | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Remove oil pads from pit and clean pit | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.3.3 | No | No | Cab forced ventilation fan shall work | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | Cab fan shall work (TKE quoted) | 4/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Machine Room Ceiling panels need to be replaced (2nd violation: 2019 and 2020) | 9/10/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Resecure machine room smoke detector to ceiling (2nd violation: 2019 and 2020) | 9/10/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)6 | No | No | Detector edge shall work independent of cab lighting circuit (reinspection needed) | 9/10/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit Scavenger pump shall be removed. Reinspection needed | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Remove oil pads from pit and clean pit | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP shall be kept in equipment room, including Testing Procedure and Fire service testing log, recorded monthly. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm shall work with power loss. (Faulty button) | 9/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Missing upthrust roller, 2nd floor door. | 9/16/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects | 10/24/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have proper Fire Extinguisher, missing. | 11/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Remove rust from pit equipment , repaint, investigate/repair water leak. | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. Provided by Elev Co | 11/16/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019) | 11/16/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK. (Dials repeatedly, never connects | 10/24/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Must make Emergency Light operable. 8.6.4.15 | 8/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency alarm operable. 8.6.4.15 | 8/13/2024 |