Inspection
Inspection Details
Equipment ID
19779
19779
Inspection Date
9/1/2020
9/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Jeffrey VanZant
Jeffrey VanZant
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
28F/28R
28F/28R
External ID
bcfe58c8-f3ef-4121-a495-ebf7a50ec593
bcfe58c8-f3ef-4121-a495-ebf7a50ec593
Location
New Academic Conference Center
601 LACLEDE AVE, NEOSHO, MO
Phone: (417) 451-3223
601 LACLEDE AVE, NEOSHO, MO
Phone: (417) 451-3223
Owner
Attn: Crpwder
Crowder College- Neosho
601 LACLEDE AVE, NEOSHO, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Crowder College- Neosho
601 LACLEDE AVE, NEOSHO, MO 64850
Phone: (000) 000-0000
Email: accountspayable@crowder.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone will not call out | 7/29/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Non-elevator related items shall not be stored in Machine Room. | 9/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | Replace missing hoistway door guides and ensure all guides have fire tabs engaging into landing sill | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location. (REINSPECTION within 30 days) | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Non-elevator related items shall not be stored in Machine Room. | 9/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Non-elevator related items shall not be stored in Machine Room. | 7/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired | 4/27/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | 11 CSR 40-5.100(2) : Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert displayed expired 2019) | 11/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | G(1)/A17.1-2016:8.6.1.2.1(a)/2.40 Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) | 11/16/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work. Dials repeatedly, never connects. (REINSPECTION 14days to REDTAG) | 10/24/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work. Dials repeatedly, never connects. (REINSPECTION 14days to REDTAG) | 10/24/2022 |