Inspection
Inspection Details
Equipment ID
2527
2527
Inspection Date
8/21/2020
8/21/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Thomas Nash
Thomas Nash
Relief Valve Pressure
Slide
Instantainous
Instantainous
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
2d4fd2e3-3b13-4b67-8a75-3c397b3d23f0
2d4fd2e3-3b13-4b67-8a75-3c397b3d23f0
Location
Hearnes Multipurpose Bldg
E STADIUM BLVD AT TIGER AVE, COLUMBIA, MO
Phone: (573) 882-6463
E STADIUM BLVD AT TIGER AVE, COLUMBIA, MO
Phone: (573) 882-6463
Owner
Attn: Jennifer Smith - Facility Operations
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | No emergency telephone | 8/21/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | No audible indication of Phase 1 Fire Service Recall | 8/21/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 4/1/2021 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(b) | No | No | Profide safe access to overhead govenor installation, current vertical ladder in excess of 20ft with access door extending over ladder while opening. a plate form must be provided to stand on while opening door. Access must be OSHA compliant, door must be marked "danger elevator hoistway" | 4/1/2021 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | A remote stop switch and a light should be installed at overhead govenor which is a remote work space to provide a safe working environment | 4/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Provide a light in top of hoistway at goverence with 10 switch on wall outside access door | 9/24/2021 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | A remote stop switch should be installed in overhead when governor is located | 1/28/2026 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(f) | No | No | Provide lighting in governor overhead which is a remote work space tp provide a safe working enviroment | 1/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Light in hoistway was not working on day of inspection | 1/28/2026 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | A remote stop switch should be installed in overhead where Governor is located | 1/28/2026 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Provide lighting in governor overhead which is a remote work space, to provide a safe working environment | 1/28/2026 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Light in hoistway was not working on day of inspection | 1/28/2026 |