Inspection
Inspection Details
Equipment ID
12540
12540
Inspection Date
8/26/2020
8/26/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Vincent Langendoerfer
Vincent Langendoerfer
Relief Valve Pressure
Slide
14"@387 fpm
14"@387 fpm
Governor Rope Pull
60/750
60/750
Door Closing Force
26
26
External ID
c8544e96-3dd4-482e-a556-75ef0ffd6099
c8544e96-3dd4-482e-a556-75ef0ffd6099
Location
St. Louis Centre East Garage
420 N 6TH ST, SAINT LOUIS, MO
Phone: (314) 231-9108
420 N 6TH ST, SAINT LOUIS, MO
Phone: (314) 231-9108
Owner
Attn: Land Clearance for Redevelopment
Land Clearance for Redevelopment
1520 Market St, Rm 2000, St. Louis, MO 63103
Phone: (000) 000-0000
Land Clearance for Redevelopment
1520 Market St, Rm 2000, St. Louis, MO 63103
Phone: (000) 000-0000
Billing
Attn: Jason Striegel
St. Louis Parking
1617 S 3rd Street, St. Louis, MO 63101
Phone: (314) 241-7777 Ext: 103
Alt Phone: (314) 231-9108
Fax: (877) 310-9169
Email: jstriegel@stlouisparking.com
St. Louis Parking
1617 S 3rd Street, St. Louis, MO 63101
Phone: (314) 241-7777 Ext: 103
Alt Phone: (314) 231-9108
Fax: (877) 310-9169
Email: jstriegel@stlouisparking.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | Yes | No | The car shall have forced ventilation conforming to A17.1 2005 - 2.14.2.3.3 with the capacity of at least one air change per minute based on net inside car volume and an auxiliary power source capable of providing the minimum air handling capacity for a continuous period of at least 1 hour. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Machine room wiring shall be enclosed. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | All wireway and electrical devices covers shall be installed. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | Yes | No | The crosshead data tag shows an incorrect number and size of ropes. A tag meeting the requirements of 2.20.2 shall be installed. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.13 - Emergency exit | 2.14.1.10 | Yes | Yes | The side emergency exit shall be permanently fixed in the closed position and the switch shall be removed. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | Yes | No | The platform guard (apron) is 37" and should be 48". The pit is of inadequate depth to support a 48" toe guard. A variance may need to be applied for. | 10/8/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 2.15.9 | No | No | The platform guard (apron) is 37" and should be 48". The pit is of inadequate depth to support a 48" toe guard. A variance may need to be applied for. | 7/7/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 12/17/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and fire service log are missing. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | AC unit shall work in machine room for climate control. |