Inspection
Inspection Details
Equipment ID
1224
1224
Inspection Date
8/17/2020
8/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
280
280
Slide
Governor Rope Pull
Door Closing Force
20F/12R
20F/12R
External ID
cfcdedd2-a79c-4fa2-801e-c56989973b21
cfcdedd2-a79c-4fa2-801e-c56989973b21
Location
St. Charles High School
725 N KINGSHIGHWAY ST, SAINT CHARLES, MO
Phone: (636) 946-1229
725 N KINGSHIGHWAY ST, SAINT CHARLES, MO
Phone: (636) 946-1229
Owner
Attn: St. Charles R-6 School Dist
St. Charles R-6 School Dist
3800 W Clay, SAINT CHARLES, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
St. Charles R-6 School Dist
3800 W Clay, SAINT CHARLES, MO 63301
Phone: (636) 443-4880
Email: tringling@stcharlessd.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 5/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light shall be operational. | 1/4/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The alarm bell shall be operational on main and auxiliary power. | 1/4/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/19/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The "G" level hall push button shall be operational. | 8/19/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 7/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. Water was pumped out of pit but pit floor needs to be cleaned of oil residue. | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The bottom limit switch cover is missing and shall be replaced. | 7/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/22/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The cover for the limit switch assembly in the pit is missing and shall be replaced. | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Per MO State Memorandum 006, oil line from jack head going into tank in machine room is no longer allowed. Oil must go into a container in the pit, no larger than 5 gallons and not permitted to overflow. | 7/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it | 7/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Battery lowering unit is not working. | 4/29/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working on battery back up. | 4/29/2026 |