Inspection
Inspection Details
Equipment ID
14138
14138
Inspection Date
9/8/2020
9/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
da483ee7-bf79-47d8-a426-d2b5e88d88c6
da483ee7-bf79-47d8-a426-d2b5e88d88c6
Location
Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 268-2768
1465 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 268-2768
Owner
Attn: Leslie Thornburg
SSM-Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO 63104
Phone: (816) 518-9214
Email: Leslie.Thornburg@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO 63104
Phone: (816) 518-9214
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 201 | Yes | No | The car buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required | 6/4/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 7/7/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5c Receptacles | No | No | A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test phase I & II fire service. Re-inspection required | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Elevator pit lighting does not work, needs repaired | |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. |