Inspection
Inspection Details
Equipment ID
18364
18364
Inspection Date
8/26/2020
8/26/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
660
660
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
22/24
22/24
External ID
c08b6512-a6f0-493d-80d3-5a61d744bc5d
c08b6512-a6f0-493d-80d3-5a61d744bc5d
Location
Saint Louis Galleria
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 863-5500
1155 SAINT LOUIS GALLERIA, RICHMOND HEIGHTS, MO
Phone: (314) 863-5500
Owner
Attn: Saint Louis Galleria
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117
Phone: (314) 571-7006
Email: nancy.gorman@brookfieldpropertiesretail.com
General Growth Properties
1155 SAINT LOUIS GALLERIA, SAINT LOUIS, MO 63117
Phone: (314) 571-7006
Email: nancy.gorman@brookfieldpropertiesretail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Main c.o.p. alarm bell inoperative on emergency power, repair | 5/17/2019 | |
| conversion | conversion | conversion - reinspect | x | Replace all missing hoistway door sight guards at terminal floors | 5/17/2019 | |
| conversion | conversion | n/a | Clean pit | 1/15/2020 | ||
| A17.1-1996 : Elevators | 2.36 - Hydraulic Cylinders | 1004.2(b)(19) | Repack left cylinder - excessive leaking. | 1/15/2020 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | Clean pit. | 2/19/2020 | |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | Replace cylinder gland packing seals. | 12/5/2023 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit. | 12/5/2023 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Place current state operating certificate in elevator machine room | 11/30/2023 | ||
| A17.1-2016 : Elevators | 2.35 - Supply Line and Shutoff Valve | 8.11.3.1.2(w) | While conducting pressure test noticed oil shooting back into the tank from the Victaulic fitting in the tank. REINSPECT REQUIRED | 6/6/2022 | ||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | Car door restrictor shall work through-out hoistway | 9/16/2024 | |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | x | Car gate switch (rear) shall not register "closed" at greater than 2" open. | 9/16/2024 | |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light (rear) shall work | 9/16/2024 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell (rear switch) shall work with loss of main 120v power. | 9/16/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Phase 1 switch halo to be replaced (unreadable and not proper color) | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Car top lighting does not work. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A code compliant MCP and related on-site documentation shall be provided. Note: No oil or fire service log for 2022 or 2023. | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Current state operating permit shall be displayed. | |||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris. | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | Machine room shall be kept clean. | |||
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Evacuation procedures are missing from the MCP. | |||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | The top of the car shall be kept clean. | |||
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing log is missing from the MCP. |