Inspection
Inspection Details
Equipment ID
14747
14747
Inspection Date
6/19/2018
6/19/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
16 lbs
16 lbs
External ID
Location
Residenses at Forest Park Hotel
4910 W Pine, St. Louis, MO
Phone: (314) 367-3300
4910 W Pine, St. Louis, MO
Phone: (314) 367-3300
Owner
FWC
206 Peach Way, Columbia, MO 65203
206 Peach Way, Columbia, MO 65203
Billing
Attn: FPA Investments
206 Peach Way, , MO 65203
206 Peach Way, , MO 65203
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | emergency alarm and phone back-up battery inoperative repair | 11/11/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm and phone back up battery inoperative. Repair | 10/18/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall include written records and procedures for inspections in machine room. | 11/11/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher in machine room needs to be serviced. | 11/11/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm does not work | 7/25/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm inoperable, does not work on emergency power or regular power. Re-inspection required | 4/1/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car to fast. Slide shall have a minimum of 2 inches and a maximum of 16 inches. Slide is 1 inch. Car has been red tagged and removed from service until the safeties are adjust and reinspected | 4/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable | 4/4/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Car safeties are stopping the car to fast. Slide shall have a minimum of 2 inches and a maximum of 16 inches. Slide is 1 inch. Car has been red tagged and removed from service until the safeties are adjust and reinspected | 6/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable | 6/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell is inoperable. Re-inspection required |