Inspection
Inspection Details
Equipment ID
9804
9804
Inspection Date
8/24/2020
8/24/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Failed
Failed
Governor Rope Pull
40/220
40/220
Door Closing Force
22
22
External ID
e69e70df-96b4-4543-93ae-fa86c796d04d
e69e70df-96b4-4543-93ae-fa86c796d04d
Location
Edward Jones Dome
901 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 342-5094
901 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 342-5094
Owner
Attn: America's Center
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101
Phone: (314) 342-5118
America's Center
701 CONVENTION PLZ, SAINT LOUIS, MO 63101
Phone: (314) 342-5118
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperative. | 8/24/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lights are inoperative. | 8/24/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | Full load car safety test failed due to governor jaw malfunction. Repair governor jaws and retest pull through force and perform car safety test with full load. Red tagged elevator until repaired and reinspected. | 2/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide on-site maintenance control program. | 4/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace deteriorating hitch plate isolation bushings. | 4/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each unit | 4/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Current type ABC Fire Extinguisher shall be hung in machine room | 4/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Hoist rope hitch plate bushings are deteriorated, replace same | 4/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace all missing braille plates on hoistway door jambs as needed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Repair leaking seal(s) on machine drive sheave | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A copy of the MCP shall be kept in the machine room for each unit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Hoist rope hitch plate bushings are deteriorated, replace same |