Inspection
Inspection Details
Equipment ID
16838
16838
Inspection Date
9/9/2020
9/9/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
cd41d65b-2635-4f49-a000-50df310a7ffb
cd41d65b-2635-4f49-a000-50df310a7ffb
Location
Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 268-2768
1465 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 268-2768
Owner
Attn: Leslie Thornburg
SSM-Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO 63104
Phone: (816) 518-9214
Email: Leslie.Thornburg@ssmhealth.com
SSM-Cardinal Glennon Childrens Hospital
1465 S GRAND BLVD, SAINT LOUIS, MO 63104
Phone: (816) 518-9214
Email: Leslie.Thornburg@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. | 1/15/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 7/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 7/9/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are rouged and undersized, need to replace ropes. Re-inspection required | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work on battery backup, need to replace battery. Re-inspection required | 7/27/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is covered in dust and debris. The pit shall be cleaned. | 7/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 7/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 7/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 8/4/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are rouged and undersized, need to replace ropes. Re-inspection required | 8/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. | 8/4/2026 |