Inspection
Inspection Details
Equipment ID
6174
6174
Inspection Date
8/25/2020
8/25/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
James Mueller
James Mueller
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
40/800
40/800
Door Closing Force
22
22
External ID
bc941356-ec87-4f85-98b5-fbdeff702436
bc941356-ec87-4f85-98b5-fbdeff702436
Location
Hoctor Building
1016 W COLUMBIA ST, FARMINGTON, MO
Phone: (573) 631-1222
1016 W COLUMBIA ST, FARMINGTON, MO
Phone: (573) 631-1222
Owner
SORTS
1016 W COLUMBIA ST, FARMINGTON, MO 63640-2902
1016 W COLUMBIA ST, FARMINGTON, MO 63640-2902
Billing
Attn: OA Facilities Mgt.-Interagency
301 W HIGH ST RM 780, JEFFERSON CITY, MO 65101-1517
301 W HIGH ST RM 780, JEFFERSON CITY, MO 65101-1517
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | Yes | No | An emergency power test with 125% capacity shall be performed and witnessed. | 12/2/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase I operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase II operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Check door force. | 7/12/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 1 testing of car safeties, check slide..Car stopped running. | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work on backup power and be answered 24/7. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Top final limit switch was not actuated before counterweights compressed buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Bottom final limit switch activates just as car compresses buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, elevator ceased operation during testing. Need to perform the following tests to complete inspection: all fire service, pit equipment and get slide measurement. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 10/7/2025 |