Inspection
Inspection Details
Equipment ID
3448
3448
Inspection Date
9/10/2020
9/10/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Bryan Henson
Bryan Henson
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
98b357f7-7be9-483d-8cd9-ac29914417fc
98b357f7-7be9-483d-8cd9-ac29914417fc
Location
Macy's- Joplin
359 N PARK AVE, JOPLIN, MO
Phone: (417) 782-6500
359 N PARK AVE, JOPLIN, MO
Phone: (417) 782-6500
Owner
Attn: RICARDO FELICIANO-CRUZ
MACY’S MSOC VERTICAL COMPLIANCE
237 WOODBRIDGE CENTER DR 3rd, WOODBRIDGE, NJ 07095
Phone: (732) 734-3436
Email: maria.castronova@macys.com
MACY’S MSOC VERTICAL COMPLIANCE
237 WOODBRIDGE CENTER DR 3rd, WOODBRIDGE, NJ 07095
Phone: (732) 734-3436
Email: maria.castronova@macys.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit need to be dry & clean--water in pit | 10/15/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | machine room door needs to be locked--key needs to be accessible to technician | 10/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Repair/Replace damaged 2nd floor unlocking device cover. | 12/9/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing button on 1st floor side hall station or install blank panel. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | : Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 3/2020) | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | H(5) Machine room lighting needs to be repaired | |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Cab lighting shall be repaired, only 1 fixture currently working. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing button on 1st floor side hall station or install blank panel. | 12/9/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | H(5) Machine room lighting needs to be repaired | 12/9/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Cab lighting shall be repaired, only 1 fixture currently working. | 12/9/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing button on 1st floor side hall station or install blank panel. | 2/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | : Machine Room Fire Extinguisher shall have current monthly/annual test tag. (Expired 3/2020) | 2/3/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | H(5) Machine room lighting needs to be repaired | 2/3/2021 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Cab lighting shall be repaired, only 1 fixture currently working. | 2/3/2021 |