Inspection
Inspection Details
Equipment ID
25304
25304
Inspection Date
8/17/2020
8/17/2020
Inspection Type
New Installation
New Installation
Inspector Name
Wayne Coder
Wayne Coder
Mechanic Name
Gregory Mason
Gregory Mason
Relief Valve Pressure
534
534
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
26dc90b2-7260-4061-8004-a3e4863680a1
26dc90b2-7260-4061-8004-a3e4863680a1
Location
Eureka High School
4525 Hwy 109, Eureka, MO
Phone: (000) 000-0000
4525 Hwy 109, Eureka, MO
Phone: (000) 000-0000
Owner
Attn: Rockwood School District
Rockwood School District
4525 Hwy 109, Eureka, MO 63025
Phone: (000) 000-0000
Rockwood School District
4525 Hwy 109, Eureka, MO 63025
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Install a code data plate. It shall read: A17.1a - 2005 and A17.1s - 2005. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures are missing from the MCP. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A code data tag is required in the machine room. | 8/15/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/7/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 8/15/2025 |
| A17.1-2016 : Elevators | 1.16 - Rated load, platform area, and data plate | 2.16.3 | No | No | The capacity plate inside the car is missing and shall be replaced. It shall be located in a conspicuous position inside the car. | 8/15/2025 |
| A17.1-2016 : Elevators | 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches | 3.29 | No | No | 3.29.1 - The car operating panel identification plate is missing and shall be replaced. | 8/15/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Category 5 testing of the valve shall be conducted on or before the next annual inspection. | 8/15/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/15/2025 |